Desc: Configuring automatic UPS shutdowns
File: shutdown.txt
Date: 2 February 2002
Auth: Russell Kroll <rkroll@exploits.org>

Old driver notice
=================

If you are using any drivers that don't support ups.conf/upsdrvctl yet, 
you will need to call them individually.  This will be repeated later in
this document.

Shutdown design
===============

When your UPS batteries get low, the operating system needs to be brought
down cleanly.  Also, the UPS load should be turned off so that all devices
that are attached to it are forcibly rebooted.

Here are the steps that occur when a critical power event happens:

1. The UPS goes on battery

2. The UPS reaches low battery (a "critical" UPS)

3. The upsmon master notices and sets "FSD" - the "forced shutdown"
   flag to tell all slave systems that it will soon power down the load.

4. upsmon slave systems see "FSD" and:

   - generate a NOTIFY_SHUTDOWN event
   - wait FINALDELAY seconds - typically 15
   - call their SHUTDOWNCMD
   - disconnect from upsd when killed by init

5. The upsmon master system waits up to HOSTSYNC seconds for the slaves
   to disconnect from upsd.  If any are connected after this time,
   upsmon stops waiting and proceeds with the shutdown process.

6. The upsmon master:

   - generates a NOTIFY_SHUTDOWN event.
   - waits FINALDELAY seconds - typically 15.
   - creates the POWERDOWNFLAG file - usually /etc/killpower
   - calls the SHUTDOWNCMD

7. On most systems, init takes over, kills your processes, syncs and
   unmounts some filesystems, and remounts some read-only.

8. init then runs your shutdown script.  This checks for the
   POWERDOWNFLAG, finds it, and tells the UPS driver(s) to power off
   the load.

9. The system loses power.

10. Time passes.  The power returns, and the UPS switches back on.

11. All systems reboot and go back to work.

How you set it up
=================

1. Make sure your POWERDOWNFLAG setting in upsmon.conf points somewhere
   reasonable.  Specifically, that filesystem must be mounted when your
   shutdown script runs.

2. Edit your shutdown scripts to check for the POWERDOWNFLAG so they know
   when to power off the UPS.  You must check for this file, as you don't
   want this to happen during normal shutdowns!

   If you can use upsdrvctl to control your drivers, something like this
   will probably work.  Change the paths to suit your system:

   if (test -f /etc/killpower)
   then
      echo "Killing the power, bye!"
      /usr/local/ups/bin/upsdrvctl shutdown
   fi

   Make sure the filesystem containing upsdrvctl and your UPS
   driver(s) is mounted when the system gets to this point.

   *** Old driver notice: if your driver(s) can't be controlled through
       upsdrvctl, you must shut them down individually, like this:

   if (test -f /etc/killpower)
   then
      echo "Killing the power, bye!"
      /usr/local/ups/bin/bestfort -k /dev/ttyS0
   fi

Multiple UPS shutdowns
======================

If you have multiple UPSes connected to your system, chances are that you
need to shut them down in a specific order.  The goal is to shut down
everything but the one keeping upsmon alive at first, then you do that one
last.

To set the order in which your UPSes receive the shutdown commands, define
the "sdorder" value in your ups.conf.

	[bigone]
		driver = apcsmart
		port = /dev/ttyS0
		sdorder = 2

	[littleguy]
		driver = bestups
		port = /dev/ttyS1
		sdorder = 1

	[misc]
		driver = fentonups
		port = /dev/ttyL2
		sdorder = 0

The order runs from 0 to the highest number available.  So, for this
configuration, the order of shutdowns would be misc, littleguy, and then
bigone.

If you have a UPS that shouldn't be shutdown when running "upsdrvctl
shutdown", set the sdorder to -1.

Testing shutdowns
=================

To see how upsdrvctl will behave without actually turning off power, use
the -t argument.  It will display the sequence without actually calling
the drivers.

Other issues
============

You may delete the POWERDOWNFLAG in the startup scripts, but it is not
necessary.  upsmon will clear that file for you when it starts.

Remember that some operating systems unmount a good number of filesystems
when going into read-only mode.  If the UPS software is installed to /usr
and it's not mounted, your shutdowns will fail.  If this happens, either
make sure it stays mounted at shutdown, or install to another partition.

Power races
===========

There is a situation where the power may return during the shutdown
process.  This is known as a race.  Here's how we handle it.

"Smart" UPSes typically handle this by using a command that forces the UPS
to power the load off and back on.  This way, you are assured that the
systems will restart even if the power returns at the worst possible
moment.

Contact closure units (ala genericups), on the other hand, have the
potential for a race when feeding multiple systems.  This is due to the
design of most contact closure UPSes.  Typically, the "kill power" line
only functions when running on battery.  As a result, if the line power
returns during the shutdown process, there is no way to power down the
load.

The workaround is to force your systems to reboot after some
interval.  This way, they won't be stuck in the halted state with the UPS
running on line power.

Know your hardware
==================

UPS equipment varies from manufacturer to manufacturer and even within
model lines.  You should test the shutdown sequence on your systems before
leaving them unattended.  A successful sequence is one where the OS halts
before the battery runs out, and the system restarts when power returns.